Get in touch with Toplit Transformer Co., Ltd Company
How we use your enquiry information: Privacy Policy.
An oil immersed transformer places the core and winding assembly inside a tank of insulating liquid, so the same fluid does two jobs at once: it insulates the live parts and it carries heat away from them. The terms oil filled transformer and liquid filled transformer describe the same construction, and American specifications usually use the liquid-filled wording. Talite builds this construction from 30–3,150 kVA on the 6, 6.3 and 10 kV classes, and from 50 to 2,500 kVA on the 35 and 38.5 kV classes.
| What The Enquiry Says | What It Means On This Page |
|---|---|
| Oil Immersed Type Transformer | The same construction, named from a different specification tradition |
| Oil Filled Transformer, Dielectric Liquid Filled Transformer | Also the same construction; the liquid-filled wording is the American habit |
| Oil Filled Distribution Transformers | The same units described by their grid role rather than by their insulation, which is how most utility and contractor enquiries arrive |
| Three Phase Oil Immersed Transformer | The three-phase member of the family, which covers almost every distribution order placed from this page |
| Oil Immersed Self Cooled Transformer | Cooling by natural circulation with no fan and no pump, carrying the ONAN designation |
Buyers arrive at this page with a kVA number and a voltage pair, not with a product name. Below, the Five-Family Duty Router turns those two inputs into the right page in one step. Each card answers the same five questions so the families can be compared side by side rather than read one at a time.
Once the Five-Family Duty Router has narrowed the family, this section fixes the numbers inside it. You’re likely going to be sizing against a peak load the network operator has already fixed rather than against a number you are free to choose, because the operator wants the rating set as close to real peak load as the connection rules allow. That means the envelope below is a screening tool, and the binding numbers come from your electrical schedule.
| Field | Published value | How it is fixed |
|---|---|---|
| Rated capacity, 10 kV class | 30–3,150 kVA | Selected from the published per-rating schedule |
| Rated capacity, 35 kV class | 50 to 2,500 kVA | Selected from the published 35 kV schedule |
| High voltage | 6, 6.3 or 10 kV; 35 or 38.5 kV | Stated in your enquiry |
| Low voltage | 0.4 kV | Stated in your enquiry |
| Vector group | Yyn0 or Dyn11 | Model dependent, confirmed on the data sheet |
| Tap range | ±5% or ±2 × 2.5% | Model dependent, confirmed on the data sheet |
| Rated frequency | Confirmed per project | Stated in your enquiry and fixed at drawing approval |
| Normal service conditions | Altitude up to 1,000 m, ambient −25 °C to +40 °C | From the supplied normal-service data |
Frequency is the field that most often separates a specification written for one market from equipment built for another. It is also one of the five tests the United States uses to decide whether a unit is covered equipment at all. We fix it with you in writing before the design is released, and we do not treat it as a default.
Altitude up to 1,000 m and ambient −25 °C to +40 °C is the normal-service band published for this construction class, which is the band set out in IEC 60076-1, published in Europe as EN 60076-1
Conditions outside that band trigger an engineering review of the temperature-rise basis rather than an assumed derating factor
Humidity, contamination, coastal salt and seismic duty are separate inputs and are handled on the drawing, not by a footnote
Two loss schedules are published for the 10 kV class: the S11-M sealed series and the S13-M energy-saving series. Subtracting one from the other rating by rating gives the S11-to-S13 Loss Delta Curve below, which is the number that decides operating cost rather than the number printed largest on a brochure.
| Rated Capacity | S11-M No-Load Loss | S13-M No-Load Loss | Difference | Reduction |
|---|---|---|---|---|
| 30 kVA | 100 W | 80 W | 20 W | 20.0% |
| 50 kVA | 130 W | 100 W | 30 W | 23.1% |
| 63 kVA | 140 W | 110 W | 30 W | 21.4% |
| 80 kVA | 150 W | 130 W | 20 W | 13.3% |
| 100 kVA | 200 W | 150 W | 50 W | 25.0% |
| 125 kVA | 240 W | 170 W | 70 W | 29.2% |
| 160 kVA | 290 W | 200 W | 90 W | 31.0% |
| 200 kVA | 330 W | 240 W | 90 W | 27.3% |
| 250 kVA | 400 W | 290 W | 110 W | 27.5% |
| 315 kVA | 480 W | 340 W | 140 W | 29.2% |
| Rated Capacity | S11-M No-Load Loss | S13-M No-Load Loss | Difference | Reduction |
|---|---|---|---|---|
| 400 kVA | 570 W | 410 W | 160 W | 28.1% |
| 500 kVA | 680 W | 480 W | 200 W | 29.4% |
| 630 kVA | 810 W | 570 W | 240 W | 29.6% |
| 800 kVA | 980 W | 700 W | 280 W | 28.6% |
| 1000 kVA | 1150 W | 830 W | 320 W | 27.8% |
| 1250 kVA | 1360 W | 970 W | 390 W | 28.7% |
| 1600 kVA | 1640 W | 1170 W | 470 W | 28.7% |
No-load loss reduction from S11-M to S13-M at each rating, computed from the two schedules in the table above. The dashed red line is the 30% figure the category markets on; the dotted black line is what these two schedules actually average. Sixteen of the seventeen ratings sit below the red line.
Short-circuit impedance in the published S11-M schedule steps from 4.0% to 4.5% at 630 kVA. United States rules draw their own line in a different place, and the two are often confused.
| Rating Band | Published Impedance | Federal Normal Range, Three-Phase Liquid-Immersed | Position |
|---|---|---|---|
| 30 to 63 kVA | 4.0% | 1.0–4.5% for 15 ≤ kVA < 75 | Inside the range |
| 80 to 100 kVA | 4.0% | 1.0–5.0% for 75 ≤ kVA < 112.5 | Inside the range |
| 125 to 400 kVA | 4.0% | 1.2–6.0% for 112.5 ≤ kVA < 500 | Inside the range |
| 500 to 630 kVA | 4.0–4.5% | 1.5–7.0% for 500 ≤ kVA < 750 | Inside the range |
| 800 to 3,150 kVA | 4.5% | 5.0–7.5% for 750 ≤ kVA ≤ 5000 | Below the lower bound |
The published schedule gives oil mass for every rating, and that number feeds a calculation most transformer pages never mention. United States facilities count qualifying oil-filled equipment toward their aggregate aboveground oil capacity, and only containers of 55 gallons or more are counted at all.[2]
| Rated Capacity | Oil Mass | Approximate Volume | Counts Toward The 55-Gallon Threshold |
|---|---|---|---|
| 100 kVA | 115 kg | about 35 US gallons | No |
| 200 kVA | 170 kg | about 52 US gallons | No |
| 250 kVA | 190 kg | about 58 US gallons | Yes, first rating to cross |
| 630 kVA | 320 kg | about 98 US gallons | Yes |
| 1000 kVA | 570 kg | about 175 US gallons | Yes |
| 1600 kVA | 750 kg | about 230 US gallons | Yes |
| 3150 kVA | 1180 kg | about 362 US gallons | Yes |
Transformer fit-and-finish are the easiest things to judge from a photograph and among the least common reasons a supplier loses a framework position. Test evidence and delivery logistics are what remove suppliers from bid lists, sometimes for years at a time, so this section leads with what you receive rather than with what we claim.
Factory acceptance testing, type testing and third-party inspection are available on request, and witness attendance is arranged with the order rather than negotiated after the unit is built. Acceptance criteria are written into the approved data sheet before production starts, so a disagreement about whether a result passes has a document to settle it.
If you treat an oil-immersed unit as a serviceable asset, with fluid condition checked on a schedule, bushings and protection devices inspected and alarms acted on, service life is counted in decades. Treated as sealed-and-forgotten equipment, the fluid becomes the first thing to fail. That is why the document pack carries the service parameters and not only the pass or fail lines.
For equipment covered by United States energy-conservation standards, the obligation to certify compliance sits with the manufacturer or the importer of record, not with the specifying engineer. That obligation is a market fact rather than a product feature, and which party carries it on your order is settled in the contract. We identify the applicable route with you during the technical review.
| Test | Federal Criterion | Where the Answer Comes From |
|---|---|---|
| Input line voltage | 34.5 kV or less | Your network voltage |
| Output line voltage | 600 V or less | Your secondary voltage |
| Frequency | Operation at 60 Hz | Confirmed in writing before design release |
| Capacity, liquid-immersed | 10 kVA to 5000 kVA | The rating you select |
| Excluded types | Thirteen named types, including special-impedance units | The 800 kVA Impedance Threshold table above |
All five tests have to be satisfied together, and a unit that fails any one of them is outside the covered category rather than non-compliant within it.[1] The screening tool below runs the same five questions so you can check a rating before writing it into a specification.
Check covered-transformer scope against 10 CFR 431.192 or open the impedance category screen for a single rating.
Talite operates from a site of 25,000 square metres with 260 production and test machines and a technical team of more than 30 engineers, and has supplied power equipment for over three decades.
Compares the published no-load loss of the S11-M sealed series against the S13-M energy-saving series at the same rating, then converts the difference into annual energy and cost at your own tariff. No-load loss runs whenever the unit is energised, so the hours field defaults to a full year.
Checks a rating and its short-circuit impedance against the normal impedance ranges published in 10 CFR 431.192 for liquid-immersed transformers. A unit built to operate outside the normal range for its rating meets the special-impedance definition, which is one of the thirteen types excluded from the federal distribution-transformer category.
Converts the published oil mass of a rating into volume and checks it against two United States thresholds in 40 CFR 112: a container is counted only when it holds 55 US gallons or more, and a facility whose aggregate aboveground capacity stays at or below 1,320 US gallons can meet the exemption on that criterion. Federal definitions treat a transformer as oil-filled operational equipment rather than as a bulk storage container, so the provisions that apply to it differ from tank rules even though the volume still counts. This is a design-team screening aid, not a compliance determination.
Scores an enquiry against the fields that have to be present before two quotations can be compared on the same basis. Fields marked critical are the ones that change the design rather than the paperwork.
It is a transformer whose core and winding assembly sits in a tank of insulating liquid, so the fluid provides both dielectric insulation and heat transfer. Buyers also call it an oil filled transformer, or a liquid filled transformer in American specifications.
Liquid-filled transformers move heat into a fluid and then out through the tank surfaces, which supports higher power density and stronger overload behaviour. A dry-type unit uses solid insulation and air. Fire rules, enclosure, footprint, containment and load duty decide which one belongs on a given site.
Compare the guaranteed value, at the same reference temperature, with the tolerance stated. Declared losses are corrected to a reference temperature, and a figure quoted without that basis cannot be set against another supplier's figure.
No. No-load loss is incident to excitation and runs whenever the unit is energised, while load loss varies with loading. On a lightly loaded feeder the no-load column typically dominates lifetime energy cost, which is why the S11-to-S13 Loss Delta Curve on this page compares that column first.
It is a design band in the published schedule, stepping from 4.0% to 4.5%. It is a separate matter from the United States normal impedance range, which changes at 750 kVA for three-phase liquid-immersed units.
That is settled per project against five criteria: input voltage, output voltage, frequency, capacity and whether the unit falls into one of the thirteen excluded types. The 800 kVA Impedance Threshold is the one to check first: at 800 kVA and above the published 4.5% impedance sits below the federal normal range, which brings the special-impedance exclusion into play.
No. Fluid condition, bushings, protection devices, leakage risk and inspection scope all remain service items. A sealed tank removes one external interface; it does not remove the service plan.
Frequency is confirmed per project and fixed in writing before design release. It is stated in your enquiry rather than assumed, because it is one of the five criteria that decide United States coverage and because network standards differ by market.
Oil mass is published for every rating on the schedule, from 70 kg at 30 kVA to 1,180 kg at 3,150 kVA. Converted at a screening density, 250 kVA is the first rating whose fluid charge crosses 55 US gallons, which is the threshold at which a container is counted toward a United States facility's aggregate oil capacity. Federal definitions treat a transformer as oil-filled operational equipment rather than as a bulk storage container, so the applicable provisions differ even though the volume still counts.
Commercial invoice, packing list, bill of lading, certificate of origin and the routine test report are supplied with your shipment, with a fluid safety data sheet where the destination requires it. Additional test or type-test evidence is agreed in the contract before production.