Seven questions that resolve whether a configured pad-mounted unit sits inside the United States regulated distribution transformer definition, and where it lands against the current equipment standard. Answer what you know; leave the rest for drawing review. Mark the sheet, print it or save it as a PDF, and attach it to your requisition.
Is the secondary line voltage 600 V or less?
This is the single fastest exit from the regulated definition. Above 600 V output, the rule does not reach the unit.
Is the unit rated for 60 Hz operation?
Is the rating between 10 kVA and 5000 kVA, liquid-immersed?
3360 kVA sits inside this band.
Is the primary line voltage 34.5 kV or less?
23 kV sits inside this limit.
For a three-phase liquid-immersed unit of 750–5000 kVA, is the impedance inside 5.0 % to 7.5 %?
Outside the band, the unit meets the special-impedance definition and is excluded by name.
Is the range between the highest and lowest tap less than 20 % of the highest tap?
Is the unit free of every excluded type below?
Autotransformer · drive (isolation) · grounding · machine-tool (control) · nonventilated · rectifier · regulating · sealed · special-impedance · testing · tap range 20 % or more · uninterruptible power supply · welding.
If your organisation evaluates transformers on lifetime cost rather than first cost, send these four values with the drawing. They let the winding and core design land on your economics instead of on a generic loss target.
The evaluated total is the purchase price plus the capitalised no-load loss plus the capitalised load loss. The lowest evaluated total is often not the lowest purchase price, which is the point of running the calculation before the award rather than after it.
| Input | Unit | What it does |
|---|---|---|
| No-load loss capitalisation factor (A) | currency / watt | Prices the standing core loss across the service life |
| Load loss capitalisation factor (B) | currency / watt | Prices the winding loss at the loading you expect |
| Expected loading profile | per-unit of rating | Sets how much the load loss actually matters against the core loss |
| Evaluation period & discount rate | years, percent | Determines how far future losses are discounted into the award decision |